REX-C100FK02-M*AN Digital Temperature Controller
BD 28.500
Out of stock
RKC REX-C100 Temperature Controller - REX-C100FK02-M-AN
Configuration: REX-C100FK02-M-AN
RKC REX-C100 Temperature Controller Relay Output
Accessories such as cables, batteries, power supplies, manuals and software disks are sold separately unless stated otherwise above.
If you are uncertain about what is included with your purchase, or have any technical or other questions, please contact us before placing your order. We are eager to assist you in making the correct choice.
Configuration: REX-C100FK02-M-AN
RKC REX-C100 Temperature Controller Relay Output
Accessories such as cables, batteries, power supplies, manuals and software disks are sold separately unless stated otherwise above.
If you are uncertain about what is included with your purchase, or have any technical or other questions, please contact us before placing your order. We are eager to assist you in making the correct choice.
Product Details
easuring accuracy: ±0.5%FS
Cold-end compensation tolerance: ±2C can be modified by software in 0~50C
Resolution: 14 bit
Sampling cycle: 0.5 Sec
Dimensions:48 x 48 x 110 (mm) ±0.2mm
Process value (PV), Setting value (SV)
Output, alarm and self-tuning can be indicated by: LED
PIN control (including ON/OFF, step-type PID and continuous PID)
Self-tuning control
Relay output: contact capacity 250V AC 3A (resistive load)
Alarm function output: 1 way
Contact capacity of output: 250V AC 3A (resistive load)
Setting value (SV): identical to measuring range (PV)
Proportional band (P): 0~full range (ON/OFF control when set to 0)
Integral time (I): 0~3600 sec (No integral action when set to 0)
Derivative time (D): 0~3600 sec (No derivative action when set to 0)
Heat-reset proportional cycle: 1~100 sec
Detective temperature range 0 to 400C
Insulation resistance: >50M ohm(500V DC)
Insulation resistance: 1500V AC/min
Power Consumption: 10 VA
Service environment: 0~50C,
environment with no corrosive gas 30~85% RH
Cold-end compensation tolerance: ±2C can be modified by software in 0~50C
Resolution: 14 bit
Sampling cycle: 0.5 Sec
Dimensions:48 x 48 x 110 (mm) ±0.2mm
Process value (PV), Setting value (SV)
Output, alarm and self-tuning can be indicated by: LED
PIN control (including ON/OFF, step-type PID and continuous PID)
Self-tuning control
Relay output: contact capacity 250V AC 3A (resistive load)
Alarm function output: 1 way
Contact capacity of output: 250V AC 3A (resistive load)
Setting value (SV): identical to measuring range (PV)
Proportional band (P): 0~full range (ON/OFF control when set to 0)
Integral time (I): 0~3600 sec (No integral action when set to 0)
Derivative time (D): 0~3600 sec (No derivative action when set to 0)
Heat-reset proportional cycle: 1~100 sec
Detective temperature range 0 to 400C
Insulation resistance: >50M ohm(500V DC)
Insulation resistance: 1500V AC/min
Power Consumption: 10 VA
Service environment: 0~50C,
environment with no corrosive gas 30~85% RH